Connect a channel
Use the channel selection button (CH) to select a suitable channel (channels
U1..2, X1..4, Q1..4) to integrate a multi-controller channel. The LED of the se-
lected channel blinks. If the selected channel is not yet connected, the binding
LED flashes.
If there is no user intervention for 10 minutes, the multi-controller re-
turns to normal operation.
Press the binding button on the multi-controller. The LED lights up green. Re-
lease the button when the LED starts blinking.
The multi-controller restarts after successful connection.
The multi-controller is ready to connect another channel or channel group.
Connect a channel group
Functions requiring more than one channel are integrated as a channel group.
In these cases, the connection is carried out for the entire channel group.
Channel groups can be created with multifunctional outputs Q1..3 and Q4/5.
When you select the first channel of a channel group not yet integrated with
the channel selection button (CH), all LEDs of the channels available to that
channel group blink, including e.g. Q1..Q3. If the channel group is not yet
connected, the binding LED flashes.
If one of the channel groups is already connected, the individual chan-
nels of this channel group can be no longer selected when navigating.
On the other hand, no other channel group can be formed if an indi-
vidual channel is already connected.
If there is no user intervention for 10 minutes, the multi-controller re-
turns to normal operation.
If you press the channel selection button again, the channel group selection is
reduced by one channel (e.g. from Q1..Q3 to Q1..Q2, etc.).
When you reach the channel group size required for the desired function,
press the binding button on the multi-controller. The LED lights up green. Re-
lease the binding button when it starts blinking.
The multi-controller restarts after successful connection.
The multi-controller is ready to connect another channel or channel group.

Connect cooling release outputs

After specifying the rooms with cooling release output via " Extra configuration
> Rooms > Room X ", you can connect the respective cooling release output
for each room.
Main menu > Commissioning > RF connections
> Cooling release output > Room X > Connect device:
Confirm subentry "Connect device" by pressing the Menu/ok button. Activate
binding mode from one of the following devices or device channels:
66 / 134
Siemens
Building Technologies
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010