Heat (inlet)
Heat (outlet)
Cooling energy
(inlet)
Cooling energy
(outlet)
Heat and cooling
energy
When using M-bus meters, it is important that the set metering me-
dium agrees with the metering medium sent by the M-bus meter.
Otherwise, the central apartment unit displays error message "Wrong
metering medium".
Configure hot water meter
You can record up to 4 hot water meters with the central apartment unit.
An allocation type and name is assigned to each hot water meter.
Main menu > Commissioning > Basic configuration
> Meter > Hot water > Hot water X > Hot water X:
Main menu > Commissioning > Basic configuration
> Meter > Hot water > Hot water X > Allocation:
A hot water meter is activated as soon as the source is set to unequal "---".
Main menu > Commissioning > Basic configuration
> Meter > Hot water > Hot water X > Source:
Configure cold water meter
You can record up to 4 cold water meters with the central apartment unit.
An allocation type and name is assigned to each cold water meter.
Main menu > Commissioning > Basic configuration
> Meter > Cold water > Cold water X > Cold water X:
Main menu > Commissioning > Basic configuration
> Meter > Cold water > Cold water X > Allocation:
A cold water meter is activated as soon as the source is set to unequal "---".
Main menu > Commissioning > Basic configuration
> Meter > Cold water > Cold water X > Source:
Siemens
Building Technologies
Heat meter installed in flow.
Heat meter installed in return. (Factory setting)
Cooling energy meter installed in flow.
Cooling energy meter installed in return.
Combine heat/cooling energy meter. This setting
makes sense only if an M-bus capable meter is
used.
Synco™ living
Commissioning the system
33 / 134
CE1C2740en
13.12.2010