Start Value; Calibrate Date And Year; Synergyr Meter Number - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Start value

When connecting meters via a pulse input, the meter value must be entered
as start value to match the central apartment unit display to that of the meter.
Entry is in digits without commas. Eight digits are available (see page 54).
For the start value, you can only enter as many decimals as start
value as displayed on the central apartment unit. The decimal places
displayed on the central apartment unit are visible when setting the
unit factor (see page 55).
Example:
Meter display = 2.375 m
Unit factor = Liters x 10 = 8 8 8 8 8 8 . 8 8 m
Start value = 00000237 (without 3
Main menu > Commissioning > Extra configuration
> Meter > ... > Start value:
Factory setting

Calibrate date and year

When partially migrating a Synergyr plant, you can enter the date of the last
calibration for each meter.
Main menu > Commissioning > Extra configuration
> Meter > ... > Calibration date:
Main menu > Commissioning > Extra configuration
> Meter > ... > Calibration year:
Calibration date
Calibration year

Synergyr meter number

Assign a Synergyr meter number to each meter when partially migrating a
Synergyr plant.
Main menu > Commissioning > Extra configuration
> Meter > ... > Synergyr meter no.:
---
No Synergyr meter number assigned (factory setting).
Meter 1
Heat meter in apartment.
Meter 2
Meter connected to the pulse input of the WRV8x or WRI80
to be replaced.
Meter 3
Meter connected to the 1st pulse input of the 1st pulse
adapter AEW2.1 of the apartment.
Siemens
Building Technologies
3
3
rd
decimal place, as the value on the central
apartment unit only uses 2 decimal places).
00000000
Factory setting
1.1
2000
Synco™ living
Commissioning the system
57 / 134
CE1C2740en
13.12.2010