Configure Domestic Hot Water (Qax913 Only) - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Minimum limitation of the return temperature
Maximum limitation of the return temperature
Main menu > Commissioning > Basic configuration
> Room groups > Room group X > Return temp limit:
---
Minimum
Maximum

Configure domestic hot water (QAX913 only)

If there is a request for DHW, the room group pumps are not put into
operation. For this reason, DHW must from a hydraulics point of view
always be installed upstream of the room groups.
Siemens
Building Technologies
Minimum limitation of the return temperature (maintained
boiler return temperature) ensures protection of the boiler
by preventing the return temperature from falling below a
certain level. Minimum limitation is accomplished by re-
ducing the flow temperature setpoint. As a result, a smal-
ler volume of boiler water is supplied to the room group
and more to the return via the bypass.
Maximum limitation of the return temperature prevents
the return temperature from exceeding a certain level,
thus ensuring better efficiencies of boilers and heat
pumps.
Maximum limitation is accomplished by supplying a smal-
ler volume of boiler water to the room group (valve posi-
tion).
Inactive – no return temperature limitation
(factory setting).
Minimum limitation of the return temperature.
Maximum limitation of the return temperature.
Synco™ living
Commissioning the system
If you want the central apartment unit
to directly control DHW charging, ac-
tivate the required DHW plant com-
ponents (DHW sensor, pump/valve,
electric immersion heater).
If you want KNX TP1 to remotely
control external DHW heating, acti-
vate "Operation external DHW".
25 / 134
CE1C2740en
13.12.2010