Connect supervision components (QAX913 only)

The following supervision components are assigned appropriate inputs or out-
puts:
• Supervision contact
• Supervision state
• Water shutoff valve
• Gas shutoff valve
• Status output 1 – 4

Connect supervision contact

Inform the QAX913 central apartment unit that you want to connect an input to
connect a supervision contact:
Main menu > Commissioning > RF connections > Supervision
> Supervision contact > Connect device:
The following device channels can be connected:
• Universal input B of a heating circuit controller (see page 62).
• Universal input Xx of a multi-controller (see page 65).

Connect supervision state

Inform the QAX913 central apartment unit that you want to connect an output
to issue a supervision state:
Main menu > Commissioning > RF connections > Supervision
> Supervision state > Connect device:
The following device channels can be connected:
• Universal relay output Qx of a multi-controller (see page 65).
• Universal relay output Qx of a heating circuit controller (see page 62).

Connect water shutoff valve

Inform the QAX913 central apartment unit that you want to connect an output
to control a water shutoff valve:
Main menu > Commissioning > RF connections > Supervision
> Water shutoff valve > Connect device:
The following devices or device channels can be connected:
• Universal relay output Qx of a multi-controller (see page 65).
• Universal relay output Qx of a heating circuit controller (see page 62).
• RF adapter plug KRF960 (see page 72).
76 / 134
Siemens
Building Technologies
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010