Pulse Valency Numerator And Denominator - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Main menu > Commissioning > Extra configuration
> Meter > ... > Unit factor:
Heat/cooling energy
Electricity
Hot/cold water
Gas
Other

Pulse valency numerator and denominator

Each pulse corresponds to a specific amount of consumption when connect-
ing meters via a pulse input. Pulse valency is printed on the meter. The pulse
valency (numerator and denominator) and unit factor must match.
Procedure for entry:
If pulse valency (e.g. liters/pulse) and the unit factor (e.g. liters) are set, the
nominator/denominator to be entered (1..9999 each) is determined as shown
below:
1. example:
Pulse valency = 20 liters/pulse
Unit factor = Liters x 10
Your setting:
Pulse
valency
=
Unit
factor
10
 Pulse valency numerator = 2 and pulse valency denominator = 1
2. example:
Pulse valency = 2.5 liters/pulse
Unit factor = Liters x 100
Your setting:
Pulse
valency
=
Unit
factor
100
 Pulse valency numerator = 1 and pulse valency denominator = 40
Main menu > Commissioning > Extra configuration
> Meter > ... > P'valency num:
Main menu > Commissioning > Extra configuration
> Meter > ... > P'valency denom:
P'valency num
P'valency denom
56 / 134
Siemens
Building Technologies
Factory setting
Wh
ml
20
2
=
1
2
.
5
1
=
40
Factory setting
1
1
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010