Exhaust hood
Impact of window switches
For operation of the exhaust hood, at least one of the windows in one of the
rooms defined here must be open.
Main menu > Settings > Exhaust hood > Imp window switches:
Factory setting
Handheld control (QAX913 only)
Buttons of the handheld control can be assigned already at the service level
and are described in the operating instructions.
Function test water detector
To check the water detector function, dip both contacts in water.
The following actions are triggered e.g. depending on the configuration set
during commissioning:
– Shutoff valve of main line closes.
– Indoor siren is sounded.
– An associated alarm is displayed on the central apartment unit.
The pending alarm must be acknowledged on the central apartment unit to al-
low the safety shutoff valve to reopen, the siren to turn off and the alarm to be
resolved:
Main menu > Faults > Acknowledge faults:
The alarm cannot be acknowledged for as long as the water detector
is immersed in water, or the alarm is reactivated immediately.
Device information
VVS-ID
From the current software and memory data (software version, EEPROM
data, flash data) an unambiguous "Valid Version Set-ID" is produced.
This enables Siemens to unambiguously identify the software status of a cen-
tral apartment unit e.g. when a problem occurs.
Main menu > Device information > VVS-ID: