Extra Configuration; Rooms; Assign Rooms To Room Groups; Cooling Release Output - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Extra configuration

As the basic configuration does not cover all required settings, more detailed
entries are required for the following topics via the "Extra configuration" menu:

• Rooms

• Ventilation
• Meters
• Faults
Rooms

Assign rooms to room groups

Per default, all 12 rooms are assigned to room group 1. For this room group, a
common flow temperature is calculated.
You can assign individual rooms to a second room group for which an inde-
pendent flow temperature is calculated.
Main menu > Commissioning > Extra configuration
> Rooms > Room X > Room group:
Room group 1
Room group 2

Cooling release output

Specify how the cooling release output of the respective room is controlled.
Main menu > Commissioning > Extra configuration
> Rooms > Room X > Cooling release outp:
---
Via RF/S-mode
Q1 (local)
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
50 / 134
Siemens
Building Technologies
Room assigned to room group 1 (factory setting).
Room assigned to room group 2.
Inactive – cooling release output not needed
(factory setting).
Cooling release output via:
• Relay output Qx of an RRV91.. heating circuit
controller or RRV934 multi-controller.
• RF adapter plug KRF960.
• S-mode object on KNX TP1 *.
Use relay Q1 of the central apartment unit as a
cooling release output.
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010