Configure Ventilation; Function - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Configure ventilation

The central apartment unit facilitates control of apartment ventilation via the
multi-controller. For the other settings, see page 50 as well as the operating
instructions in section "Ventilation".
RRV934 Multi-controller
Q1 – Q3 3-stage step switch of ventilation plant
X1
Indoor air quality sensor
X2
Humidity sensor
ZUL
Supply air
ABL
Extract air
AUL
Outside air
FOL
Exhaust air

Function

Tell the central apartment unit about the number of stages (speeds) of the fan
used for ventilation.
Main menu > Commissioning > Basic configuration
> Ventilation > Function:
---
1-stage
2-stage
3-stage
28 / 134
Siemens
Building Technologies
Inactive – no ventilation (factory setting).
1-stage ventilation.
2-stage ventilation.
3-stage ventilation.
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010