Heat demand relay

When the appropriately defined output terminal closes, a heat demand signal
is transmitted to the heat source.
Specify if a heat demand relay is used and how it is controlled.
Main menu > Commissioning > Basic configuration
> Outputs > Heat demand relay:
---
Via RF
Q1 (local)
Heat demand DC 0..10 V
The current heat demand can be transmitted to the heat source in the form of
a DC 0..10 V signal.
The temperature values corresponding to DC 0 V and 10 V and the threshold
value for a valid heat request can be set (see page 119).
Specify if the DC 0..10 V heat demand output is used and how it is controlled.
Main menu > Commissioning > Basic configuration
> Outputs > Heat dem DC 0...10 V:
---
Via RF

Refrigeration demand relay

When the appropriately defined output terminal closes, a refrigeration demand
signal is transmitted to the refrigeration source.
Specify if a refrigeration demand relay is used and how it is controlled.
Main menu > Commissioning > Basic configuration
> Outputs > Refrig demand relay:
Siemens
Building Technologies
Inactive – heat demand relay not needed
(factory setting).
Relay output Qx of an RRV91... heating circuit con-
troller or RRV934 multi-controller used as a heat
demand relay.
Relay output Q1 of the central apartment unit used
as a heat demand relay.
Inactive – DC 0..10 V heat demand output not re-
quired (factory setting).
Universal output U of the RRV912... heating circuit
controller or the RRV934 multi-controller used as a
DC 0..10 V heat demand output.
Synco™ living
Commissioning the system
45 / 134
CE1C2740en
13.12.2010