Humidity limitation
This function monitors the relative humidity of the air and compares it with the
set "Humidity limit value".
If the relative humidity exceeds the limit value, the ventilation system is
switched on at the preselected stage to remain on until the humidity has
dropped one switching differential below the limit value.
The relative humidity level (r.h.) is displayed on the central apartment unit.
In certain cases, the ventilation system is not capable of reducing the humidity
to the required level.
To prevent the ventilation system from operating continuously in such cases,
settings "Running time" and "Pause time" can be used to set an interval for
operation.
Interval mode is switched off again when the relative humidity drops one
switching differential below the limit value.
r.h.
Relative humidity
r.h. max
Humidity limit value
SD
Switching differential of humidity limitation
I
Interval mode active (ON/OFF)
V ON
Fan on, "Running time humidity limitation"
V OFF
Fan off, "Pause time humidity limitation"
Switching differential of humidity limitation
If the ventilation system was switched on because humidity in the room was
too high, it is switched off again when humidity drops below the "Humidity limit
value" by the switching differential set here (1..20%).
Main menu > Ventilation > Humidity limitation > Switching diff:
Factory setting
Running time humidity limitation
The humidity limitation interval starts with the running time set here (0..720 min).
During this period of time, the ventilation system operates at the preselected
stage.
108 / 134
Siemens
Building Technologies
5 %
Synco™ living
Function settings
CE1C2740en
13.12.2010