Status output 1 – 4
When the appropriate output terminal closes, the central apartment unit indi-
cates the occurrence of events via an external component (e.g. signal lamp or
horn).
The events (smoke, window/door supervision, water leak, gas leak, CO alarm,
panic, emergency, fault 1 - 3) leading to closure of the status output can be
defined via parameter "Events status output". For a description of this parame-
ter, see the Operating Instructions, section "Supervision".
Specify if a status output is used and how it is controlled.
Main menu > Commissioning > Basic configuration > Supervision
> Status output X:
---
Via RF
Q1 (local)
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).

Handheld control (QAX913 only)

Activate the required handheld control and enter the names to be used for
their display.
Main menu > Commissioning > Basic configuration > Handheld control
> Handheld control X > Handheld control X:
Main menu > Commissioning > Basic configuration > Handheld control
> Handheld control X > Function:
---
Active

Configure inputs

By closing a contact at the input terminal, the respective input function can be
triggered.
Activate the respective input function by stating from where the central apart-
ment unit receives the signal of the input terminal (Via RF/S-mode, B (local)).
40 / 134
Siemens
Building Technologies
Inactive – status output not needed (factory setting).
Deliver state of status output via:
• Relay output Qx of an RRV91.. heating circuit control-
ler or RRV934 multi-controller.
• RF adapter plug KRF960.
• S-mode object on KNX TP1 *.
Relay output Q1 of the central apartment unit used as a
status output.
Inactive – handheld control not needed (factory setting).