Pause Time Humidity Limitation; Air Humidity At 0 V/10 V; Minimum Operating Time Night Cooling; Reference Room Night Cooling - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Main menu > Ventilation > Humidity limitation > Running time:
Factory setting

Pause time humidity limitation

When the "Running time" has elapsed, the ventilation system is switched off
for the pause time set here (0..720 min) before it resumes operation.
Main menu > Ventilation > Humidity limitation > Pause time:
Factory setting

Air humidity at 0 V/10 V

Connect a humidity sensor (DC 0..10 V) to limit humidity.
The humidity sensor must be located inside the room to ensure that
air also circulates around the sensor when the ventilation system is
off. Do not install the sensor in the extract air duct.
The humidity value for 0 V and 10 V (0..100% r.h.) can be set here.
Main menu > Ventilation > Humidity limitation > Humidity 0 V:
Factory setting
Main menu > Ventilation > Humidity limitation > Humidity 10 V:
Factory setting

Minimum operating time night cooling

If all switch-on conditions for night cooling are met, it is switched on for at least
the time set here (0..720 min).
Main menu > Ventilation > Night cooling > Operating time min:
Factory setting

Reference room night cooling

To be able to determine the necessary temperature differential, the central
apartment unit requires the room temperature plus the outside temperature.
Select the reference room to indicated to the controller which of the room sen-
sors is the most suited for acquiring the reference value.
Main menu > Ventilation > Night cooling > Reference room:
Factory setting
Siemens
Building Technologies
30 min
60 min
0 % r.h.
100 % r.h.
30 min
Room 1
Synco™ living
Function settings
109 / 134
CE1C2740en
13.12.2010