DHW (QAX913 only)
Frost protection setpoint
Set the DHW setpoint to be used in Protection mode.
Main menu > DHW > Setpoints > Frost prot setp:
Guide value
Legionella setpoint
Set the setpoint the DHW storage tank should maintain during the time the le-
gionella function is performed.
Main menu > DHW > Legionella function > Legionella setpoint:
Guide value
Legionella protection frequency
Specify how often the legionella function should be activated.
It can be performed daily or weekly. With the weekly legionella function, the
weekday can be selected (Mo..Su).
Main menu > DHW > Legionella function > Legio prot freq:
Never
Legionella protection is off.
Daily
Legionella protection carried out every day.
Monday
Legionella protection carried out every Monday.
(Factory setting)
...
Sunday
Legionella protection carried out every Sunday.
Legionella protection time
Specify the time of day (00:00..24:00) the legionella function should start.
Main menu > DHW > Legionella function > Legio prot time:
Factory setting
Legionella protection period
When the legionella function is active, the DHW storage tank is maintained at
the legionella protection setpoint for the period of time set here (0.00 – 6.00
hours).
Siemens
Building Technologies
5 °C
70 °C
05:00
Synco™ living
Function settings
111 / 134
CE1C2740en
13.12.2010