Room controller settings
These settings are visible only if the user-defined heating type is set.
(See page 20).
P-band Xp
The room controller's P-band can be set for every room to suit individual
needs.
Main menu > Rooms > Room X > Room controller > P-band Xp:
For your guidance, see the default settings (factory setting 2 K):
Room type
Radiator heating slow
Radiator heating fast
Floor heating slow
Floor heating fast
Integral action time Tn
The room controller's integral action time can be set for every room.
Main menu > Rooms > Room X > Room controller > Int action time Tn:
For your guidance, see the default settings (factory setting 5400 s):
Room type
Radiator heating slow
Radiator heating fast
Floor heating slow
Floor heating fast
Siemens
Building Technologies
Guide value Xp
2 K
2 K
2 K
2 K
Guide value Tn
5400 s
3600 s
7200 s
5400 s
Synco™ living
Function settings
99 / 134
CE1C2740en
13.12.2010