Specify if a relay should be used to release the exhaust hood and how it is
controlled.
Main menu > Commissioning > Basic configuration
> Outputs > Exhaust hood:
---
Via RF/S-mode
Q1 (local)
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Configure RF repeater
Activate the required number of RF repeaters. For that, select every RF re-
peater required (1...3) and change the setting from "---" to "Active".
Main menu > Commissioning > Basic configuration
> RF repeater > Repeater X:
---
Active
Configure info pages
Windows/doors
Specify if you want to display open doors/windows (info page).
Main menu > Commissioning > Basic configuration
> Info pages > Windows/doors:
No
Yes
Business card
Specify if the business card (info page) should be displayed.
Main menu > Commissioning > Basic configuration
> Info pages > Business card:
No
Yes
48 / 134
Siemens
Building Technologies
Inactive – release of exhaust hood not required
(factory setting).
Release of exhaust hood via:
• Relay output Qx of an RRV91.. heating circuit con-
troller or RRV934 multi-controller.
• S-mode object on KNX TP1 *.
Use relay output Q1 of the central apartment unit for
release of the exhaust hood.
Inactive – RF repeater not required (factory setting).
RF repeater available.
Do not show info page (factory setting).
Show info page.
Do not show info page (factory setting).
Show info page.
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010