Configure Light State Display (Qax913 Only) - Siemens Synco living QAX913 Mounting And Commissioning

Hide thumbs Also See for Synco living QAX913:
Table of Contents

Advertisement

Enter the desired metering medium.
Main menu > Commissioning > Basic configuration
> Meter > Other > Other X > Metering medium:
Other
Oil
Steam
When using M-bus meters, it is important that the set metering me-
dium agrees with the metering medium sent by the M-bus meter.
Otherwise, the central apartment unit displays error message "Wrong
metering medium".

Configure light state display (QAX913 only)

The QAX913 central apartment unit is capable of indicating the light status of
4 selected lamps.
Each of the 4 lamps can be assigned a name which appears on the info page.
Main menu > Commissioning > Basic configuration
> Light state > Light X > Light X:
Activate one of the lamps by setting the function to "Active":
Main menu > Commissioning > Basic configuration
> Light state > Light X > Function:
---
Active
Info page "Light state" is displayed only if at least one of the 4 lamps
is activated.
To indicate the light status, switch or dim actuators of any manufac-
ture can be used which, via S-Mode KNX TP1 *, communicate with
the central apartment unit.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Siemens
Building Technologies
Other medium if no specific medium applies.
(Factory setting)
This meter is used for oil consumption.
This meter is used for steam consumption.
(e.g. in district heating).
Inactive – no light state display required.
(Factory setting)
Lamp for light state display active:
Synco™ living
Commissioning the system
35 / 134
CE1C2740en
13.12.2010

Advertisement

Table of Contents
loading