Default Value - Siemens RXB Series Basic Documentation

Knx bus communications
Table of Contents

Advertisement

Introduction
Setting values
Note
Autonomous controller
42 / 88
Siemens
Building Technologies
7.1.4
Default value "----" in series B devices
The "Geographical zone (apartment)" represents the room to be controlled. Within
this zone, all process values relevant to the room are transmitted (e.g. room
operating mode, room setpoint and measured room value, plus user intervention
and other influences).
The factory setting or default value for the RM... series B controllers is "---". This
default value indicates that the zone is "out of service", i.e. no relevant process
values are transmitted within this zone.
Main menu > Commissioning > Communication > Room
Operating line
Geographical zone
(apartment)
Time switch slave
(apartment)
Factory setting or default value "----" applies to all RM... series B controllers.
In the "Autonomous controller" application, a ventilation system is controlled
independently of other plant, according to its own room operating conditions.
For this application there is no need to set a zone address for the "Geographical
zone (apartment)", i.e. the default "---" can be left as is.
KNX bus communications
Communication via zone addresses
Range
Factory setting or default value
----, 1...126
----
----, 1...126
----
For internal use only
CE1P3127en
2013-04-08