H/C Changeover Relay And Fault Status Messages - Siemens RXB Series Basic Documentation

Knx bus communications
Table of Contents

Advertisement

Configuration
Setting values
Heating/cooling ch'over
relay
Configuration
Current contact position
Fault status messages
H/ C changeover signal
failure
Fault status message
5801
> 1 H/C changeover
signal
Fault status message
5802
For internal use only
Siemens
Building Technologies
Main menu > Commissioning > Extra configuration > Heating/cooling ch'over
Operating line
Heating/cooling acc to
calendar
Main menu > Commissioning > Settings > Heating/cooling ch'over
Operating line
Start date heating
Start date cooling
Changeover occurs on "Start date, heating" or "Start date, cooling".
9.2.4

H/C changeover relay and fault status messages

If, instead of being transmitted over the bus, the H/C changeover signal is provided
at a relay output, e.g. for switch control of a valve, or forwarding to a non-
communicating device, the H/C changeover relay can be configured accordingly.
See the notes on connecting the primary controller to the changeover valve.
Main menu > Commissioning > Extra configuration > Heating/cooling ch'over
Operating line
Heating/cooling ch'over relay
The current contact position (status) of the changeover relay can be displayed via
the Service level.
Main menu > Heating/cooling ch'over
Operating line
Heating/cooling ch'over relay
In a 2-pipe system without H/C changeover signal on the KNX bus, the controller
continues to use the last received value. If the signal never existed, "Heating" is
used as default value.
No.
Text
5801
H/C changeover
signal failure
If the "H/C changeover" in a 2-pipe system is configured so that it is initiated by
calendar or operating mode selector, and if a changeover signal is received in one
of the zones from another device, message ">1 heat/cool changeover signal" is
transmitted.
No.
Text
5802
>1 heat/cool
changeover signal
KNX bus communications
Appendix
Range
No, yes.
Range
01.01. - 31.12.
01.01. - 31.12.
Range
----, N.Q1, N.Q2,.../
Current contact position (status)
Open (Off) Cooling / Closed (On): Heating
Effect
Non-urgent message; no acknowledgement
required.
Effect
Non-urgent message; must be acknowledged.
Factory setting
No
Factory setting
01.10.
01.05.
Factory setting
----
69 / 88
CE1P3127en
2013-04-08