3. INSTALLATION
(2) How to connect/disconnect cables
(a) Connecting cables
1) The SSCNET III cable is shipped with protective tubes on the optical cord ends of the connectors.
Remove the tubes.
2) Remove the CN1A and CN1B connector caps of MR-MT2010.
3) While holding a tab on the SSCNET III cable connector, insert the connector to the CN1A and
CN1B of MR-MT2010 until you hear a clicking sound. If the optical cord ends are dirty, optical
transmission is interrupted, causing a malfunction. When they are dirty, wipe with a bonded
textile, etc. Do not use a solvent such as alcohol.
(b) Disconnection
Pull out the SSCNET III cable connector while holding a tab on the connector. When the SSCNET III
cable is removed from MR-MT2010, be sure to put caps on the connectors to protect them from
dusts. Attach the protective tubes on the optical cord ends of the connectors.
POINT
The CN1A and CN1B connectors of MR-MT2010 are capped to protect light
devices inside the connectors from dust. For this reason, do not remove a cap
until just before connecting an SSCNET III cable. Be sure to put the cap when
the SSCNET III cable is removed.
While the SSCNET III cable is connected, keep the caps for the CN1A and
CN1B connectors and protective tubes for the optical cord ends in a plastic bag
with a slide fastener provided with the SSCNET III cable to protect them from
dirt.
When requesting repair of MR-MT2010 due to malfunctions, make sure to cap
the CN1A and CN1B connectors. When the caps are not put on the connectors,
the light device may be damaged in transit. The light device needs to be
replaced for repair if damaged.
CN1A
CN1B
Tab
3 - 9
Click
CN1A
CN1B