PROFIBUS®-/PROFINET® parameter set
8
PROFIBUS
The data that the FPM exchanges with the higher-level controller via the fieldbus can be divided into input
and output data and error identifier:
In the registers the data are stored in the following format:
Fieldbus
PROFINET
, PROFIBUS
®
®
Tab. 8.1:
Transmission formats
For the input data, a distinction is made between:
FPM PROFIBUS®
FPM PROFINET
®
FPM PROFINET
M12
®
FPM PROFIBUS®
Refers to the GSD file from chapter 7.1.3 „Device master file (GSD data)" on page 22.
In this GSD file the used input addresses are divided into three blocks:
StatusModul (256 - 287): 32 Byte
ResultsModulCam (288 - 351): 64 Byte
ResultsModulPMM (352 - 391): 64 Byte
FPM PROFINET
®
Refers to the GSDML file from chapter 7.2.2 „Device master file (GSDML file)" on page 24.
In this GSDML file the used input addresses are divided into three blocks:
Status (256 - 287): 32 Byte
ResultsCam (288 - 351): 64 Byte
ResultsPMM (352 - 415): 64 Byte
FPM PROFINET
M12
®
Refers to the GSDML file from chapter 7.3.2 „Device master file (GSDML data)" on page 27.
In this GSDML file the used input addresses are divided into four blocks:
Status (256 - 287): 32 Byte
ResultsSingle (288 - 351): 64 Byte
ResultsCaustic (352 - 383): 32 Byte
ResultsPMM (384 - 447): 64 Byte
Revision 06 EN 02/2023
-/PROFINET
parameter set
®
®
Format
Motorola format, Big Endian
29