Measuring
12.1.3

Measuring procedure focus measurement (triggered)

System
Sets parameters for the measurement
(256.0 - 256.3) or
(A257.0 - 258.0 / 260 - 299)
Sets command.start (256.4)
If status.acknowledge == 1: deletes
command.start (256.4)
If status.ready_for_measurement==1:
turns on the laser (max. 2s)
Turns off the laser (after the necessary
irradiation time)
Reads out results/error identifiers
Revision 06 EN 02/2023
FPM
Deletes status.idle
(282.4)
Deletes status.measurement_finished (282.2)
Deletes Errorflags and -identification
Reads parameters for the measurement (from the setup or the profibus)
Sets status.acknowledge (282.6)
Deletes status.acknowledge (282.6)
Sets status.measurement_running (282.1)
Sets status.ready_for_measurement (282.0)
Laser is detected (trigger)
Starts the measurement
When the measurement is finished: deletes status.measurement_
running (282.1)
Deletes status.ready_for_measurement (282.0)
Calculates parameters
Enters parameters into Profibus register or error identifiers
Sets status.measurement_finished (282.2)
Sets status.idle (282.4)