• Gain Adjustment Method
① Adjust the offset before adjusting the gain.
② Set the dA-01 in USr-08 with the operator. DA is set to output 5V at this point.
(However, when 5V is not output correctly, in other words, if the voltage is not
output as set in SEt-08 and SEt-09, adjust with the following method.)
③ Measure output voltage of each channel.
④ Set SEt-72 and SEt-74 according to the calculation below.
Absolute value of D/A output voltage will increase when the setting is increased in
the standard of 100, and it will decrease when decreasing the setting. Accurate
calculation is as follows.
SEt-72 = 100 * 5[V]/Actual output voltage of channel 1 [V] (Voltage output when
the motor is in normal operation status)
SEt-74 = 100 * 5[V]/Actual output voltage of channel 2 [V] (Voltage output when
the motor is in normal operation status)
⑤ Or, by observing the output voltage, SEt-72 and SEt-74 can be set so the voltage is
5[V]. Reduce the setting if the voltage is greater than 5[V], or increase the setting
if the voltage is less than 5[V].
H. Parameter Initialization
All user parameter values except SEt-23. SEt-24. SEt-36, SEt-37, SEt-51 ~ 53, and SEt-71 ~
74 can be reset to factory setting value in USr-09.
It takes around 4 seconds to initialize the data. Wait enough time before proceeding with the
next step.
This is flickered
until the key is
selected.

Fig 4.13 Initialization of User Parameter