General Conditions; Bacnet Link - ABB FBIP-21 BACnet/IP User Manual

Table of Contents

Advertisement

66 Technical data

General conditions

Installation
Degree of protection
Ambient conditions
Package
Indicators
Connectors
Power supply
Compliance

BACnet link

Compatible devices
Medium
Topology
Transfer rate
Serial communication
type
Protocol
Into an option slot on the drive control unit
IP20
The ambient conditions specified for the drive in
its manuals are applicable.
Cardboard. Plastic wrapping: Antistatic air bubble
sheet (PE).
Three bicolor LEDs (HOST, MODULE,
NETWORK/NET)
A 20-pin connector to the drive
RJ-45 connector to Ethernet (X1)
RJ-45 connector for chaining another adapter
module (X2)
±
+3.3 V
5% max. 400 mA (supplied by the drive)
Complies with EMC standard EN 61800-3:2004
Printed circuit board conformal coated
Ethernet Standard IEEE 802.3 and IEEE 802.3u
devices
10BASE-TX or 100Base-TX with Auto-
negotiation and Auto-MDIX (Auto-crossover)
• Wiring: CAT5/6 UTP, CAT5/6 FTP, CAT5/6
STP
• Connector: RJ-45
• Termination: Internal
• Maximum segment length: 100 m / 328 ft
Bus or star.
Max. 50 nodes allowed for FBIP-21 in a daisy
chain topology.
10 Mbps or 100 Mbps
Half or full duplex
BACnet/IP

Advertisement

Table of Contents
loading

Table of Contents