Test and conditions

Table 5.2.-1
Environmental test and conditions
Recommended service temperature range
(continuous)
Transport and storage temperature range
Dry heat test
Dry cold test
Damp heat test, cyclic
Table 5.2.-2
Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test, class III
• Common mode
• Differential mode
Electrostatic discharge test, class III
• For contact discharge
• For air discharge
Radio frequency interference tests
• Conducted, common mode
• Radiated, amplitude-modulated
• Radiated, pulse-modulated
Fast transient disturbance tests
• All terminals
Surge immunity test
• Power supply
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
SPA-ZC 400
-10...+55°C
-40...+70°C according to
the IEC 60068-2-48
According to the IEC 60068-2-2
According to the IEC 60068-2-1
According to the IEC 60068-2-30
According to the IEC 60255-22-1
2.5 kV
1.0 kV
According to the IEC 61000-4-2 and IEC
60255-22-2
6 kV
8 kV
According to the IEC 61000-4-6 and
IEC 60255-22-6 (2000)
10 V (rms), f=150 kHz...80 MHz
According to the IEC 61000-4-3 and
IEC 60255-22-3 (2000)
10 V/m (rms), f=80...1000 MHz
According to the ENV 50204 and
IEC 60255-22-3 (2000)
10 V/m, f=900 MHz
According to the IEC 60255-22-4 and
IEC 61000-4-4
4 kV
According to the IEC 61000-4-5
4 kV, line-to-earth
2 kV, line-to-line
300 A/m continuous