A max. of 10 RS-485 ports: COM2, 3, 5 ~ 14. Each port can connect to up to 32 M-7000
M-7000 Series
modules. (With optional I-7510 repeater connected can connect to up to more than 32
Modbus I/O
M-7000 Modules)
Supports ICP DAS Ethernet I/O : I-8KE4-MTCP and I-8KE8-MTCP. If LAN1 malfunctions, it will
automatically switch to the 2nd Ethernet port (in optional I-8135W card) to continuously
Modbus TCP/IP I/O
work. (The IP address for LAN1 and the 2nd Ethernet's IP should be set in the same IP
domain) (FAQ-042)
Enable a max. of 3 pcs. I-8172W boards in slot 0~2 to be used to connect to FRnet I/O
FRnet I/O
modules, such as FR-2053, FR-2057, FR-32R, FR-32P. Each I-8172W board can link to a
max. of 256 DI plus 256 DO channels.
Send Email
Provide functions to send email with a single attached file via the Ethernet port.
Used to exchange data between ICP DAS ISaGRAF Ethernet PACs via the Ethernet port.
Ebus
(LAN1 Port only)
Either COM3 or COM5 can link to a GSM Modem to support SMS. The user can request
SMS: Short Message
data/control the controller via a cellular phone. The controller can also send data and
Service
alarms to the user's cellular phone.
Optional GSM Modem: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem)
COM3 or COM5 supports the ICP DAS MMICON.
MMICON/LCD
64 dot LCD & a 4 x 4 Keyboard to display picture, string, integer, float, & input a char, string,
integer & float.
UDP Server & UDP
LAN1 or the 2nd Ethernet (in optional I-8135W card) supports the UDP Server and UDP
Client :
Client protocols allowing messages to be sent/received to/from a PC/HMI or other device.
Exchange Message
For example, data can be automatically reported to the InduSoft's RXTX driver.
& Auto-report
LAN1 or the 2nd Ethernet (in optional I-8135W card) supports the TCP Client protocol
TCP Client :
allowing messages to be sent/received to/from a PC/HMI or other device that supports the
Exchange Message
TCP server protocol. For example, data can be automatically reported to the InduSoft's
& Auto-report
RXTX driver, or to connect a location camera.
Enable the I-8212W (2G/3G) card allowing short messages to be sent/received to/from or
to access a dial up connection to link to the Internet and using a GPRS connection to send
GPRS/SMS
an email or communicate with remote stations using the "FTP Client" (FAQ-151) or the
"TCP Client"/"UDP Server"/"UDP Client" (FAQ-143) protocols.
Support for the SQL Client function that allows data to be written (or read from) a
SQL Client
Microsoft SQL Server (2000 SP3, 2005, 2008).
Must enable the 2nd Ethernet port in the optional I-8135W card. This redundant system has
setup two "Active IP" address point to the active VP-2xW7/2xW6 's LAN1 and 2nd Ethernet
ports always. One or two or more PC / HMI / SCADA can communicate with this redundant
system via one of the two given active IP. So the PC / HMI / SCADA can access to the system
Hot-Swap and
easily without any notice about which VP-2xW7/2xW6 is currently active.
Redundant System
new redundant system can integrate with the RU-87P4 and RU-87P8 expansion unit plus
the I-87K high-profile I/O cards to support the hot-swap application. If the I/O card is
damaged, the maintenance person just takes one good-card with same model number to
hot-swap the damaged one without stopping this redundant system. (FAQ-093)
COM3 or COM5~14 can connect to one I-7530 (converter: RS-232 to CAN) to support
CAN/CANopen
CAN/CANopen devices and sensors. One PAC supports a max. of 10 RS-232 ports to
connect a max. of 10 I-7530.
Enable the I-8123W CANopen Master card to connect to other CANopen Slave devices.
CANopen Master
(FAQ-145)
HART Solutions
Enable I-87H17W modules in slots 0 to 2 to communicate with other HART devices.
Enable the FTP Client to upload files from the PAC to a remote FTP server on a PC.
FTP Client
(FAQ-151)
The Soft-GRAF g_Alarm and g_Logger1 HMI objects also support FTP Client. (FAQ-146)
(*)
ISaGRAF WinCE ViewPAC User Manual , V.1.6 , 1/2017 by ICP DAS
(FAQ-082,
154)
(*)
The MMICON is featured with a 240 x
(*)
(FAQ-086)
Moreover, the