1. ISaGRAF WinCE ViewPAC support only High profile I-8K and I-87K I/O cards in slot 0 to 2. Please refer
to the accompanying CD-ROM: \napdos\isagraf\vp-25w7-23w7\english-manu\ Datasheet files.
2. Please always set a fixed IP address to the ISaGRAF WinCE ViewPAC.
the NS-205/208 or RS-405/408 Industrial Ethernet Switch for them.
Note:
1. This chapter describes the programming basics for the Web HMI. We will not focus on the HTML
basics. If you want to know more about the HTML programming, the best way is to "buy a HTML
related book" from the bookstore. There are a lot of books doing this job.
2. The Web HMI only supports the basic HTML tags. It doesn't support ASP, PHP or JSP or other Page
Server language.
3. Please do not use <frameset> </frameset> , <frame> </frame> in the Web HMI.
4. Note: The object name, object ID, code, variable name and function name is case sensitive. For
example, refresh_data( ) and Refresh_data( ) is different.
5. There are more than ten Web HMI examples in the VP-25W7/23W7 CD-ROM. Please refer to the
section
3.1.
5.1

Basic Files For The Web HMI

The basic Web HMI files include 2 folders and 3 DLL files and 4 htm files as below.
Folders
1
./img/
2
./msg/
DLL Files
1
whmi_filter.dll
2
login.dll
3
main.dll
HTM Files
1
index.htm
2
login.htm
3
menu.htm
4
main.htm
User may put his own image files into the folder named as "user_img". And put user-defined
JavaScript file or css file into the folder named as "user_msg". Other folder name is not acceptable
by the ViewPAC Web HMI.
The "index.htm" file is the default entry page of the web server. User must not modify it. The
"index.htm" re-directs to the "login.htm" file in 1 to 2 seconds when someone visits the ViewPAC
via the Internet Explorer.
User may modify the "login.htm" , "menu.htm" and "main.htm" to fit the requirement.
Chapter 5
(default image files - *.jpg , *.bmp , *.gif )
(default message files – wincon.js & xxerror.htm)
(three DLL files)
(first default page)
(the Web HMI welcome page)
(the page-menu page, normally on the left on the Internet Explorer)
(first page when successfully login)
ISaGRAF WinCE ViewPAC User Manual , V.1.6 , 1/2017 by ICP DAS
Web HMI Basics
(No
DHCP). Recommend to use
5-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vp-25w7Vp-23w7Vp-4137Vp-25w6Vp-23w6Vp-4136

Table of Contents