Custom Control Level; Equations; Input Side (If) - Simplex 4005 Programming Instructions Manual

Table of Contents

Advertisement

Custom Control,

Custom Control Level

Equations

Input Side (IF)

Technical Manuals Online! - http://www.tech-man.com
Continued
After entering the statement level you can work on the individual parts of a
Custom Control statement. The display shows the current statement on the top
line with the current "field" of the statement marked with focus brackets ( [ ] ).
The current option selection is shown in focus brackets on the lower line of the
display.
Use <L> or <M> to move between the statement fields on the top line and
<Next> and <Previous> to scroll through the options for the current field (and
display the new selection) on the lower line. Press <Enter> to move the new
option from the lower line to the selected field in the top line. This also moves
the field focus to the next field.
A total of 40 Custom Control equations are possible in the 4005. A Custom
Control equation consists of up to six statements. Each equation consists of two
sides: an INPUT SIDE and an OUTPUT SIDE. An equation can be better
understood as an "IF/THEN" command. "IF" the INPUT SIDE is true, "THEN"
execute the OUTPUT SIDE.
Each equation is made up of one or more input statement and one or more output
statement (for a total of six statements). The equation in Figure 3-4 has four
statements: two input statements and two output statements.
Each input statement is made up of four fields.
FIRST STATEMENT
[ ]
Equation
Figure 3-4. An Equation
Field 1
Field 2
127
[
]
Empty field
Optional NOT
starts a
operator
Custom
Control
equation
Figure 3-5. The Four Fields of an Input Statement
3-4
Input Statement
Input Statement
End of Inputs
Output Statement
Output Statement
End of Outputs
Field 3
),5(

[
]
[
Condition
qualifier for
field 4
Continued on next page
Field 4
]
Point

Hide quick links: