Smoke Control System Custom Control Equations

Introduction

Smoke Control
System CC Equation
Summary
The following Custom Control (CC) equations are written for a 4100U/4100ES based smoke
control system. Note that the points mentioned are representative of any system. Your system will
use different points to provide the Inputs and Outputs.
The following "Custom Control Equation Summary" gives the CC equation number followed by a
label (title) for the program.
CUSTOM CONTROL EQUATION SUMMARY
Equation No.
Label
------------------- ----------------------------------------
1
SET UP NORMAL CONDITIONS AT STARTUP
2
CLEAR FAULTS ON STARTUP
3
SET NORMAL CONDITIONS AT RESET
4
REPORT TROUBLE IF SWITCHES NOT RESET
5
INITIALIZE NORMAL CONDITIONS AT RESET
6
NORMAL CONDITIONS COMPLETE AFTER RESET
7
SMOKE CONTROL INITIATE
8
SMOKE CONTROL RESET
9
INITIATE SMOKE ZONE 1
10
ACTIVATE SMOKE CONTROL ZONE 1
11
INITIATE SMOKE ZONE 2
12
ACTIVATE SMOKE CONTROL ZONE 2
13
INITIATE SMOKE ZONE 3
14
ACTIVATE SMOKE CONTROL ZONE 3
15
INITIATE SMOKE ZONE 4
16
ACTIVATE SMOKE CONTROL ZONE 4
17
SUPPLY FAN DUCT SMOKE ALARM
18
STAIR PRESS FAN DUCT SMOKE ALARM
19
REPORT TBL IF SUPPLY FAN NOT ON
20
REPORT TBL IF SUPPLY FAN NOT OFF
21
REPORT TBL IF EXHAUST FAN NOT ON
22
REPORT TBL IF EXHAUST FAN NOT OFF
23
REPORT TBL IF STAIR PRESS FAN NOT ON
24
REPORT TBL IF STAIR PRESS FAN NOT OFF
25
REPORT TBL IF MAIN EXH DAMPER NOT OPEN
26
REPORT TBL IF MAIN EXH DAMPER NOT CLOSED
27
REPORT TBL IF MAIN SUP DAMPER NOT OPEN
28
REPORT TBL IF MAIN SUP DAMPER NOT CLOSED
29
REPORT TBL IF MAIN RET DAMPER NOT OPEN
30
REPORT TBL IF MAIN RET DAMPER NOT CLOSED
31
REPORT TBL IF SUP DAMPER 1 NOT OPEN
32
REPORT TBL IF SUP DAMPER 1 NOT CLOSED
33
REPORT TBL IF SUP DAMPER 2 NOT OPEN
34
REPORT TBL IF SUP DAMPER 2 NOT CLOSED
35
REPORT TBL IF SUP DAMPER 3 NOT OPEN
36
REPORT TBL IF SUP DAMPER 3 NOT CLOSED
37
REPORT TBL IF SUP DAMPER 4 NOT OPEN
38
REPORT TBL IF SUP DAMPER 4 NOT CLOSED
39
REPORT TBL IF EXH DAMPER 1 NOT OPEN
40
REPORT TBL IF EXH DAMPER 1 NOT CLOSED
41
REPORT TBL IF EXH DAMPER 2 NOT OPEN
42
REPORT TBL IF EXH DAMPER 2 NOT CLOSED
43
REPORT TBL IF EXH DAMPER 3 NOT OPEN
5-5