Reference Information,
Analog Pseudo Card
Point Number: Description
1: Fire Alarm Count
2: Supervisory Count
3: Trouble Count
4: System Startup
5-25:
User Definable
List Pseudo Card
Point Number Description
1: System Monitors and Manual
Evacuation
2: Waterflow Monitors
3: Sprinkler Monitors
4: Primary Elevator Capture
Monitors
5: Alternate Elevator Capture
Monitors
6: Points Off with Silence
7: Points Off with Reset
8-25:
User Definable
Technical Manuals Online! - http://www.tech-man.com
Continued
Table 6-15 describes the Points associated with the Analog Pseudo Card (System
Address 30).
Table 6-15. Analog Pseudo Card (System Address 30)
Device Type
Analog Pseudo
Analog Pseudo
Analog Pseudo
Analog Pseudo
Analog Pseudo
Table 6-16 describes the Points associated with the List Pseudo Card (System
Address 31).
Table 6-16. List Pseudo Card (System Address 31)
Device Type
List Pseudo
List Pseudo
List Pseudo
List Pseudo
List Pseudo
List Pseudo
List Pseudo
List Pseudo
Point Type
Analog
Indicates the current number of
fire alarms in the system.
Analog
Indicates the current number of
supervisories in the system.
Analog
Indicates the current number of
troubles in the system
Analog
Turns on for one poll cycle at
system startup for user specific
initialization needs
Analog
Open for specific job needs and
requirements
Point Type
List
Contains all monitor zones and
the manual evacuation pseudo
point (not user editable)
List
Contains all waterflow monitors
(not user editable)
List
Contains all sprinkler monitors
(not user editable)
List
User editable list for placing
primary elevator capture monitor
zones into
List
User editable list for placing
alternate elevator capture monitor
zones into
List
User editable list for placing
points which should be turned off
with a signal silence operation
List
User editable list for placing
points which should be turned off
with a successful system reset
List
Open for specific job needs and
requirements
6-20
Purpose
Purpose