Point Type Messages for Auxiliary Relay Points,
Auxiliary Relay Points
(continued)
Technical Manuals Online! - http://www.tech-man.com
Pt. TYPE: RWATER
Description: Waterflow Relay (on until reset)
Operates on General Alarm
Circuit Status
LCD Readout (2
On
WaterFlow Relay
Off
WaterFlow Relay
WaterFlow Relay
Disabled TBL
WaterFlow Relay
Off Auto TBL
WaterFlow Relay
Detailed Description:
Used in applications where a waterflow signal circuit is
required which will remain activated until the reset key is pressed. Activated
from a zone with the point type WATER.
Figure 5-61. RWATER Point Type
Pt. TYPE: SUPV
Description: Sprinkler Supervisory Relay (on
until acknowledged)
Circuit Status
LCD Readout (2
On
Supervisory Relay
Off
Supervisory Relay
Supervisory Relay
Disabled TBL
Supervisory Relay
Off Auto TBL
Supervisory Relay
used in applications where a Supervisory signal circuit is
Detailed Description:
required which will remain ON until acknowledged.
Figure 5-62. SUPV Point Type
Pt. TYPE: RELAY
Description: Generic Relay (no default
operation)
Circuit Status
LCD Readout (2
On
Auxiliary Relay
Off
Auxiliary Relay
Auxiliary Relay
Disabled TBL
Auxiliary Relay
Off Auto TBL
Auxiliary Relay
Used for all relay applications that are not defined by a
Detailed Description:
specific point type.
Figure 5-63. RELAY Point Type
5-23
Continued
nd
line)
OFF
CODING
TROUBLE
TROUBLE
nd
line)
OFF
CODING
TROUBLE
TROUBLE
nd
line)
OFF
CODING
TROUBLE
TROUBLE
Continued on next page
LED
ON
T
T
LED
ON
T
T
LED
ON
T
T

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents