Ac Power Failure Operation; Delay Door Drop On Ac Power Failure Operation - Simplex 4005 Programming Instructions Manual

Table of Contents

Advertisement

SMPL Language Applications,

AC Power Failure Operation

Delay Door Drop on AC Power
Failure Operation
Technical Manuals Online! - http://www.tech-man.com
Continued
In the following example the 24 VDC magnetic door holders drop when any
alarm is initiated or when primary AC power is lost. This prevents excessive
current drain on the system batteries when AC is lost.
Add the following SMPL equation (see the To Start SMPL Programming section
of this publication).
AC Power Failure Equation
Equation
21&2'( 
25 $1<  ),5( 
(QG RI ,QSXW
75$&. 21  35, 
(QG RI 2XWSXW
Note:
Using TRACK causes the relay (20-01) to reenergize when AC
power is restored.
In the following example the 24 VDC magnetic door holders drop when on
alarm or 30 seconds after a power failure. If the power is interrupted for a time
less than thirty seconds, the doors will not drop.
1.
Change the Door Holder circuits point types to Relay (see the Edit Points,
Edit Point Type section of this publication).
2.
Add the following SMPL equation (see the To Start SMPL Programming
section of this publication).
Delay AC Power Failure Equation
Equation
21&2'( 
'(/$< &167  
25 $1<  ),5( 
(QG RI ,QSXW
75$&. 21  35, 
(QG RI 2XWSXW
4-11
Point Label
$& )DLOXUH 0RQLWRU
6\VWHP
0RQ
0DQXDO
Ã
à Ã
Ã
'RRU +ROGHU &LUFXLW
Point Label
$& )DLOXUH 0RQLWRU
6\VWHP
0RQ
0DQXDO
Ã
à Ã
Ã
'RRU +ROGHU &LUFXLW
Continued on next page
Point Type
(YDF
Point Type
(YDF