Input Field 3 and Input Field 4

Overview

Using the FIRE Qualifier

SECOND STATEMENT
Technical Manuals Online! - http://www.tech-man.com
Field 3 contains the condition qualifier for the point listed in Field 4; Field 4
options change per Condition Qualifier selected.
When using the input condition qualifier FIRE, a statement is true when the
point indicated in Field 4 is activated. Field 4 Choices for the FIRE qualifier are:
System Card Points
Digital Pseudo Points
Note:
When the condition of 03-01 is FIRE, the input is true, and the output is
executed. If the system is not reset, and the condition of 03-02 becomes FIRE
after 03-01, the system outputs ignore 03-02. In other words, if the output
executes from the FIRE condition of 03-01, the output does not re-execute from
the FIRE condition of 03-02.
FIRST STATEMENT
[ ]
25
[
]
Figure 3-18. An Example Where the First and the Second Statement
Example: The condition of 03-01 is FIRE. The 4005 is reset from the Fire
The statement holds true until the system is reset.
Field 1
Field 2
[ ]
Field 1
Field 2
[ ]
Both Contain the Condition FIRE
Alarm Control Panel (FACP). After the system is reset (and there
are no alarms) the condition of 03-02 is FIRE. The appropriate
notification appliances now activate for the FIRE condition of 03-02.