Simplex 4005 Programming Instructions Manual page 105

Table of Contents

Advertisement

Point Type Messages for Monitor Points,
Monitor Points (continued)
Technical Manuals Online! - http://www.tech-man.com
Pt. TYPE: SUPV
Description: Supervisory Monitor (no alarm)
Circuit Status
LCD Readout (2
Normal
Supervision Monitor
Limited
Supervision Monitor
Open
Supervision Monitor
Short
Supervision Monitor
Disable TBL
Supervision Monitor
Class A TBL
Supervision Monitor
Used to monitor any supervisory type device where
Detailed Description:
operator acknowledgement is required.
Figure 5-29. SUPV Point Type
Pt. TYPE: UTIL
Description: Utility Monitor with Tri-State (no
alarm)
Circuit Status
LCD Readout (2
Normal
Utility Monitor
Limited
Utility Monitor
Open
Utility Monitor
Short
Utility Monitor
Disable TBL
Utility Monitor
Class A TBL
Utility Monitor
Used to monitor and supervise any condition. Operator
Detailed Description:
acknowledgement is not required.
Figure 5-30. UTIL Point Type
Pt. TYPE: LATSUPV
Description: Supervisory Latching
Circuit Status
LCD Readout (2
Normal
Supervisory Monitor
Limited
Supervisory Monitor
Open
Supervisory Monitor
Short
Supervisory Monitor
Disable TBL
Supervisory Monitor
Class A TBL
Supervisory Monitor
Detailed Description:
Used for generic supervisory alarm.
Figure 5-31. LATSUPV Point Type
5-11
Continued
nd
line)
SUPERVISORY
SUPERVISORY
nd
line)
nd
line)
SUPERVISORY
SUPERVISORY
LED
NORMAL
S
TROUBLE
T
S
TROUBLE
T
TROUBLE
T
LED
OFF
ON
TROUBLE
T
ON
TROUBLE
T
TROUBLE
T
LED
NORMAL
S
TROUBLE
T
S
TROUBLE
T
TROUBLE
T
Continued on next page