Input Field 3 and Input Field 4,
Using the FIRE ACK Qualifier
SECOND STATEMENT
Using the SUPV Qualifier
Technical Manuals Online! - http://www.tech-man.com
When using the input condition qualifier FIRE ACK (Fire Acknowledge), a
statement is true when the point indicated in Field 4 is activated. Field 4
Choices for the FIRE ACK qualifier are:
•
•
Note:
FIRST STATEMENT
[ ]
[ ]
Figure 3-20. An Example Where the First and the Second Statement
Example: The condition of 03-01 is FIRE ACK. The input of the equation
When using the input condition qualifier SUPV (Supervisory), a statement is true
when the point indicated in Field 4 is activated. Field 4 Choices for the SUPV
qualifier are:
•
•
Note:
FIRST STATEMENT
[ ]
Figure 3-21. An Example That Contains the Condition SUPV
Example: The condition of 03-01 is SUPV. The input of the equation remains
Continued
System Card Points
Digital Pseudo Points
The statement holds true until the point indicated in Field 4 is
Acknowledged. The Output operator used for the example below
is TRACK.
Field 1
Field 2
[ ]
Field 1
Field 2
[ ]
Both Contain the Condition FIRE ACK
remains true until the point indicated in Field 4 is acknowledged
from the FACP. The same holds true for 03-02.
System Card Points
Digital Pseudo Points
The statement holds true until the point indicated in Field 4 clears.
Field 1
Field 2
[ ]
true until the point indicated in Field 4 is cleared.
3-13
Field 3
Field 4
),5( $&.
[
] [
Field 3
Field 4
),5( $&.
[
] [
Field 3
Field 4
6839
[
]
[
Continued on next page
]
]
]