Using The Or And Not Operators - Simplex 4005 Programming Instructions Manual

Table of Contents

Advertisement

Input Field 2,
Using the OR and NOT
Operators
SECOND STATEMENT
Technical Manuals Online! - http://www.tech-man.com
Continued
The OR Link operator links the current statement in Parallel with all previous
statements in an equation (see Figure 3-16).
FIRST STATEMENT
[ ]
25
[
]
In Figure 3-17, if the condition of 03-01 is Fire OR the condition of 03-02 is
NOT Fire then the INPUT SIDE is true. In order to cross from the INPUT SIDE
of the equation to the OUTPUT SIDE, the first or the second statement must be
true.
Note:
INPUT SIDE
(Statements 1 & 2)
Figure 3-17. An Example of How the NOT Operator Works In Parallel
Field 1
Field 2
[ ]
Field 1
Field 2
127
[
]
Figure 3-16. An OR Link and a NOT Operator
The NOT gate is shown as a normally closed contact. This
statement is true because there is a path from the Input to the
Output.
03-01
18-01
18-02
03-02
3-10
Field 3
Field 4
),5(

[
]
[
Field 3
Field 4
),5(

[
]
[
OUTPUT SIDE
This statement is true because
03-01 is not in the FIRE
condition and 03-02 is not in
the FIRE condition.
]
]

Hide quick links: