Smpl Programming; Edit Smpl; Sample Program; Valid Operator Codes And Parameter Tables - Simplex 4005 Programming Instructions Manual

Table of Contents

Advertisement

SMPL Programming

Edit SMPL

Sample Program

Valid Operator Codes and
Parameter Tables
Technical Manuals Online! - http://www.tech-man.com
The Edit SMPL function has the following parameters:
Max. number of Equations: 40
Max. number of Statements (Input or Output combined) per Equation: 6
01: Input Side
ALARM 18-01
OR DETECT 18-04
End of Input
HOLD ON 20-01 PRI 9,9
End of Output
02: Input Side
ON 28-01
End of Input
HOLD OFF 20-01 PRI 9,9
End of Output
Tables 6-2 through 6-4 show valid operator codes that are supported from front
panel programming.
Table 6-2. SMPL Input Qualifiers Table
OPCODE (Qualifier)
FIRE DET
FIRE
FIRE ACK
SUPV
SUPV ACK
TBL
TBL ACK
ON/CODE
COMP CNST
OFF
ANY
ALL
DELAY CNST
Table 6-3. SMPL Input Operators Table
OPCODE
MNEMONIC
29
NOT
31
AND
30
OR
6-5
(where 18 is the card address number
and 01/ 04 is the point number)
(where 9,9 indicates the point's set
and reset priorities respectively)
DESCRIPTION
Fire Detect State
Fire State
Fire Acknowledge State
Supervisory State
Supervisory Acknowledge State
Trouble State
Trouble Acknowledge State
Oncoding State
Compare to a constant value
Off State
Any Number of elements in a List
All element in a List
Delay for a constant value
DESCRIPTION
NOT operator
AND operator
OR operator
Continued on next page

Hide quick links:

Advertisement

Table of Contents
loading