Installation and start-up
June 2022
Analog inputs settings switches
Figure 4-25
Figure 4-25: Customer wiring for analog inputs
A. Backplane
B. Analog inputs
C. Analog input 1
D. Analog input ground
E. Analog input 2
F. Cable
G. Customer devices
H. Customer 4-20 mA outputs
Figure 4-26
the base input/output (I/O) board. These analog inputs are set to accept a current (4-20
mA) source.
Figure 4-26: Factory settings for analog input switches
Use the Hardware → Analog Inputs menu in Rosemount MON2020 to configure the
analog inputs.
Note
To set an analog input to accept a voltage (0-10 VDC) source, flip the appropriate switch in
the opposite direction from that shown in
84
shows how to wire two analog inputs (TB10).
shows the factory settings for the analog input switches that are located on
Figure
4-26.
Reference Manual
2-3-9000-744