Equipment description and specifications
June 2022
2.2.1
Electronics hardware
Type
Communication (standard)
Communication (optional)
Ethernet
40
Specifications
•
Analog inputs:
—
Two standard 4-20 mA inputs filtered with transient protection
•
Analog outputs:
—
Six isolated outputs, 4–20 mA
•
Serial communication ports:
—
Three termination blocks
—
Configurable as RS-232, RS-422, or RS-485
—
One D-sub (9-pin) port for personal computer (PC) connection
•
Digital inputs:
—
Five inputs, user assignable
—
Optically isolated, rated to 30 Vdc at 0.5 A
•
Digital outputs:
—
Five outputs, user assignable
—
Form C and electro-mechanically isolated, 24 Vdc
Four expansion slots available for additional communications. Each slot has the
capacity to add one of the following:
•
Four analog inputs (isolated) card
•
Four analog outputs (isolated) card
•
Eight digital inputs (isolated) card
•
Five digital outputs (isolated) card
•
One RS-232, RS-422, or RS-485 serial connection card (up to two maximum)
Two available connections
•
One RJ45 port
•
One 4-wire termination – with 10/100 Mbps
Reference Manual
2-3-9000-744
Emerson.com/Rosemount