Profibus Dp Fieldbus Couplers/Controllers 750-333(/0Xx-000), 750-833(/0Xx-000); Table 39: General Module/Channel Parameters - WAGO -I/O-SYSTEM 750 Manual

2ai pt100/rtd 2-channel analog input module for resistance sensors
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

54
Appendix
Table 38: Specific Module/Channel parameters for 75x-461/003-000
Parameter
Filter
Filter constant
Overrange protection
User scaling
Offset
Gain
Vendor scaling
*)
Default setting
8.1.2.2
PROFIBUS DP Fieldbus Couplers/Controllers
750-333(/0xx-000), 750-833(/0xx-000)
The aforementioned fieldbus coupler/ controller allow module-specific
parameterization of behavior at diagnosis.

Table 39: General Module/Channel parameters

Parameter
Diagnosis
Channel x (x = 0...1)
*)
Default setting
Value
I/O-CHECK
*)
activated
deactivated
12.5 Hz, 500 ms
*)
25 Hz, 250 ms
50 Hz, 125 ms
60 Hz, 110 ms
100 Hz, 65 ms
200 Hz, 32 ms
400 Hz, 15 ms
*)
activated
deactivated
activated
*)
deactivated
*)
0x0000 (0)
*)
0x0100 (256)
*)
activated
deactivated
Value
*)
0 (disabled)
1 (enabled)
WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
WAGO
GSD file
PB-DP
Explanation
The fieldbus coupler/controller signals a
diagnosis if the I/O module reports the events:
External fault
Measuring range underflow
Wire break
Diagnostics reported by the I/O module do not
lead to the signaling of a diagnosis by the
fieldbus coupler/controller.
Diagnostics reported by the I/O module lead to
the signaling of a diagnosis by the fieldbus
coupler/controller.