I-87018/ 87018R/ 87019R
Range Code
Thermocouple
(Hex)
0E
0F
10
11
12
13
14
15
16
17
18
19
Thermocouple Type Definition
Type
J Type
2's Complement HEX
K Type
2's Complement HEX
T Type
2's Complement HEX
E Type
2's Complement HEX
R Type
2's Complement HEX
S Type
2's Complement HEX
B Type
2's Complement HEX
N Type
2's Complement HEX
C Type
2's Complement HEX
L Type
2's Complement HEX
M Type
2's Complement HEX
L Type
DIN43710
2's Complement HEX
CAN-8x23 user's manual (Revision 3.20, Mar/08/2012) ------
Data Format
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Input Range
Back to table
Max Value
Min Value
+760.00℃
-210.00℃
7FFF
DCA2
+1372.0℃
-0270.0℃
7FFF
E6D0
+400.00℃
-270.00℃
7FFF
A99A
+1000.0℃
-0270.0℃
7FFF
DD71
+1768.0℃
+0000.0℃
7FFF
0000
+1768.0℃
+0000.0℃
7FFF
0000
+1820.0℃
+0000.0℃
7FFF
0000
+1300.0℃
-0270.0℃
7FFF
E56B
+2320.0℃
+0000.0℃
7FFF
0000
+800.00℃
-200.00℃
7FFF
E000
+100.00℃
-200.00℃
4000
8000
+900.00℃
-200.00℃
7FFF
E38F