I-87019R
Range
Code (Hex)
00
-15mV to +15mV
01
-50mV to +50mV
02
-100mV to +100mV
03
-500mV to +500mV
04
05
-2.5V to +2.5V
-20mA to +20mA
06
with 125Ω resistor
08
(default)
09
0A
Type 00 to 19 Definition
Input Range
-1V to +1V
-10V to +10V
-5V to +5V
-1V to +1V
CAN-8x23 user's manual (Revision 3.20, Mar/08/2012) ------
Data Format
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Back to table
Negative
Full Scale
Full Scale
+15.000 mV -15.000 mV
7FFF
8000
+50.000 mV -50.000 mV
7FFF
8000
+100.00 mV -100.00 mV
7FFF
8000
+500.00 mV -500.00 mV
7FFF
8000
+1.0000 V
-1.0000 V
7FFF
8000
+2.5000 V
-2.5000 V
7FFF
8000
+20.000 mA -20.000 mA
7FFF
8000
+10.000 V
-10.000 V
7FFF
8000
+5.0000 V
-5.0000 V
7FFF
8000
+1.0000 V
-1.0000 V
7FFF
8000
191