ICP DAS USA CAN-8823 User Manual page 190

Canopen slave device
Table of Contents

Advertisement

I-87018 Series
Range Code
(Hex)
00
-15mV to +15mV
01
-50mV to +50mV
02
-100mV to +100mV
03
-500mV to +500mV
04
05
(default)
-20mA to +20mA
*1
06
with 125Ω resistor
Note:
*1: When I-87018 and I-87018R are connecting to a current source set to 06 type code,
an optional external 125 Ohms resistor is required.
Type 00 to 06 Definition
Input Range
-1V to +1V
-2.5V to +2.5V
CAN-8x23 user's manual (Revision 3.20, Mar/08/2012) ------
Data Format
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Input Range
2's Complement HEX
Back to table
Negative
Full Scale
Full Scale
+15.000 mV
-15.000 mV
7FFF
+50.000 mV
-50.000 mV
7FFF
+100.00 mV
-100.00 mV
7FFF
+500.00 mV
-500.00 mV
7FFF
+1.0000 V
-1.0000 V
7FFF
+2.5000 V
-2.5000 V
7FFF
+20.000 mA
-20.000 mA
7FFF
8000
8000
8000
8000
8000
8000
8000