13.1.1 POWER (POW) Indicator Lamp (Statuses: ON, flashing, OFF)

Lamp
status
ON
Flashing
OFF

13.1.2 RUN Indicator Lamp (Statuses: ON, OFF)

Lamp
status
ON
OFF
13.1.3 BATT (BAT) Indicator Lamp (Statuses: ON, OFF) [FX
Lamp
status
ON
OFF
13.1.4 ALM Indicator Lamp (Statuses: ON, OFF) [FX
This LED is valid when the optional battery is installed and the battery mode is selected using a parameter.
Lamp
status
ON
OFF
Downloaded from
ManualsNet.com
/FX
/FX
PLC User's Manual - Positioning Control Edition
3U
3UC
Status of PLC
The specified voltage is properly
supplied to the power supply terminal.
The PLC may be at one of the following
statuses:
· The specified voltage/current is not
supplied to the power supply
terminal.
· An external line is not properly
connected.
· The PLC has a problem.
The PLC may be at one of the following
statuses:
· The power is off.
· The specified voltage is not
supplied to the power supply
terminal.
· The power cable is disconnected.
Status of PLC
The sequence program is being
executed.
Execution of the sequence program is
stopped.
Status of PLC
The voltage of the battery is too low.
The battery supplies enough voltage as
specified by D8006.
Status of PLC
The voltage of the battery is too low.
The battery supplies enough voltage as
specified by D8006.
search engine
Troubleshooting
The power is being supplied properly.
· Check the power supply voltage.
· Excluding the power cable, disconnect all other cables, and
then turn the power ON again. Check the lamp status. If the
lamp flashes again, please contact your local Mitsubishi
Electric representative.
If the power is on, check the power supply unit and the power supply
line.
If the power is properly supplied, please contact your local Mitsubishi
Electric representative.
Troubleshooting
The RUN indicator lamp indicates the operation status of the PLC.
Note that the RUN indicator lamp will go out depending on the status
of the ERROR indicator lamp (refer to Subsection 13.1.4).
/FX
3U
Troubleshooting
Immediately replace the battery (refer to the manual of the PLC).
The PLC has no problems.
/FX
]
3G
3GC
Troubleshooting
Immediately replace the battery (refer to the manual of the PLC).