Built-in Positioning Functions
6) CLEAR signal output
This instruction can output the CLEAR signal after stopping at the origin.
If it is necessary to output the CLEAR signal at the completion of zero return, turn on the "CLEAR signal
output function enable" relay (see the following table).
Use an FX
output device.
a) If it is not necessary to use the CLEAR signal device specification function, or if an FX
b) If it is necessary to use the CLEAR signal device specification function:
7) Zero return speed
Use the devices shown in the following table to set the zero return speed. Be sure to set the zero return
speed so that the relation with the other speeds is "bias speed  zero return speed  maximum speed".
8) Creep speed
Use the devices shown in the following table to set the creep speed. Be sure to set the creep speed so
that the relation with the other speeds is "bias speed  creep speed  maximum speed".
B - 104
Downloaded from
ManualsNet.com
/FX
/FX
PLC User's Manual - Positioning Control Edition
3U
3UC
PLC Ver. 2.20 or later and FX
3UC
Ver. 2.20 is used.
Pulse output
signal output function
destination device
= Y000
D
1
= Y001
D
1
= Y002
D
1
= Y003
D
1
Turn on the "CLEAR signal device specification function enable" relay to specify the CLEAR signal
output device (output Y) for the pulse output destination device using the CLEAR signal device
specification register.
 For an example program, refer to Subsection 4.3.4 or Subsection 4.5.1.
Pulse output
signal output function
destination device
= Y000
D
1
= Y001
D
1
= Y002
D
1
= Y003
D
1
-
If "zero return speed > maximum speed", the operation will be performed at the maximum speed.
Pulse output
Bias speed
destination device
D8342
= Y000
D
1
D8352
= Y001
D
1
D8362
= Y002
D
1
D8372
= Y003
D
1
Pulse output
Bias speed
destination device
D8342
= Y000
D
1
D8352
= Y001
D
1
D8362
= Y002
D
1
D8372
= Y003
D
1
search engine
/FX
/FX
3S
3G
Status of "CLEAR signal
Status of "CLEAR
device specification function
enable" relay
M8341=ON
M8351=ON
M8361=ON
M8371=ON
Status of "CLEAR signal
Status of "CLEAR
device specification function
enable" relay
M8341=ON
M8351=ON
M8361=ON
M8371=ON
Zero return speed
D8347,D8346
D8357,D8356
D8367,D8366
D8377,D8376
Creep speed
D8345
D8355
D8365
D8375
6 Mechanical Zero Return - DSZR/ZRN Instruction
6.2 DOG Search Zero Return (DSZR Instruction)
/FX
PLC to specify the CLEAR signal
3GC
3U
CLEAR signal device
enable" relay
M8464=OFF
M8465=OFF
M8466=OFF
M8467=OFF
CLEAR signal device
specification register
*1
enable" relay
M8464=ON
M8465=ON
M8466=ON
M8467=ON
Maximum speed
D8344,D8343
D8354,D8353
D8364,D8363
D8374,D8373
Maximum speed
D8344,D8343
D8354,D8353
D8364,D8363
D8374,D8373
PLC below
3UC
number
Y004
Y005
Y006
Y007
D 8464
D 8465
D 8466
D 8467
Initial value
50,000(Hz)
Initial value
1,000(Hz)