Fx 3G Series Main Unit (Transistor Output - Mitsubishi Electric FX3S Series User Manual

Hide thumbs Also See for FX3S Series:
Table of Contents

Advertisement

FX
/FX
/FX
3S
3G
3GC
Built-in Positioning Functions
2.5.2
FX
3G
This section describes the transistor output specifications of the FX
simultaneous turning-on rate is restricted for the output extension units and the main unit. For details on this
restriction, refer to the following manual.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
External voltage
Maximum
load
Open-circuit leakage current
ON voltage
Response
time
Circuit insulation
Indication of output motion
Pulse output terminals Y000, Y001, and Y002
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC).
*1.
Operation voltage range
Operation current range
Downloaded from
ManualsNet.com
/FX
/FX
PLC User's Manual - Positioning Control Edition
3U
3UC
Series main unit (Transistor Output)
Item
Resistance load
Inductive load
OFFON
14-point, 24-point
type
ONOFF
OFFON
40-point, 60-point
type
ONOFF
Y002 works as a high-speed response pulse output terminal only in 40-point and 60-point type main
units.
Item
Output frequency
search engine
Transistor output specifications
All outputs
5 to 30 V DC
The total load current of resistance loads per common
terminal should be the following value or less.
All outputs
- 1 point output common:0.5 A
- 4 points output common:0.8 A
The total of inductive loads per common terminal
should be the following value or less.
All outputs
- 1 point output common:12 W/24 V DC
- 4 points output common:19.2 W/24 V DC
All outputs
0.1 mA or less at 30 V DC
All outputs
1.5 V or less
5 s or less at 10 mA or more (5 to 24 V DC)
Y000, Y001
Y002 or more 0.2 ms or less at 200 mA or more (at 24 V DC)
5 s or less at 10 mA or more (5 to 24 V DC)
Y000, Y001
Y002 or more 0.2 ms or less at 200 mA or more (at 24 V DC)
Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC)
Y003 or more 0.2 ms or less at 200 mA or more (at 24 V DC)
Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC)
Y003 or more 0.2 ms or less at 200 mA or more (at 24 V DC)
All outputs
Photocoupler insulation
All outputs
LED is lit when the photocoupler is driven.
*1
are high-speed response output terminals.
Description
5 to 24 V DC
10 to 100 mA
100 kHz or less
2.5 Output Specifications
Series main unit. Note that the
3G
Refer to the FX
Hardware Edition.
3G
2 Specifications
A
B
Apx.
B - 31

Advertisement