INVT Goodrive 200L Operation Manual page 179

Table of Contents

Advertisement

inverters
Goodrive200L
or more.
It is necessary to add fuse for the avoidance of overload.
It is appropriate to use a breaker (MCCB) which complies with the inverter power in the
3-phase AC power and input power and terminals (R, S and T). The capacity of the inverter
should be 1.5-2 times of the rated current.
 Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases may
escape from the breaker enclosure in case of a short-circuit. To ensure
safe use, special attention must be paid to the installation and
placement of the breakers. Follow the manufacturer's instructions.
Inverter
GD200-0R7G-4
GD200-1R5G-4
GD200-2R2G-4
GD200-004G/5R5P-4
GD200-5R5G/7R5P-4
GD200-7R5G/011P-4
GD200-011G/015P-4
GD200-015G/018P-4
GD200-018G/022P-4
GD200-022G/030P-4
GD200-030G/037P-4
GD200-037G/045P-4
GD200-045G/055P-4
GD200-055G/075P-4
GD200-075G/090P-4
GD200-090G/110P-4
GD200-110G/132P-4
GD200-132G/160P-4
GD200-160G/185P-4
GD200-185G/200P-4
GD200-200G/220P-4
GD200-220G/250P-4
GD200-250G/280P-4
GD200-280G/315P-4
GD200-315G/350P-4
GD200-350G/400P-4
GD200-400G-4
GD200-500G-4
Breaker (A)
10
10
16
16
25
40
50
63
63
80
100
125
160
160
250
250
315
350
400
500
500
630
630
700
800
800
1000
1200
174
Rated current of the
Fuse (A)
16
16
16
25
32
40
50
63
80
100
125
160
160
200
250
315
315
400
500
630
630
630
800
800
1000
1000
1250
1250
Appendix C
reactor (A)
12
12
12
12
25
25
40
40
50
65
80
95
115
150
185
225
265
330
400
500
500
500
630
630
780
780
780
980