INVT Goodrive 200L Operation Manual page 136

Table of Contents

Advertisement

inverters
Goodrive200L
Fault
code
UPE
Parameters uploading fault
Parameters downloading
DNE
PROFIBUS/CANOPEN
E-Dp
Communication fault
Fault type
fault
Possible cause
 The connection of the
keypad wires is not
good or broken
 The keypad wire is too
long and affected by
strong interference
 There is circuit fault on
the communication of
the keypad and main
board
 The connection of the
keypad wires is not
good or broken
 The keypad wire is too
long and affected by
strong interference
 There is mistake on
the data storage of the
keypad
 Surrounding inference
is stronge.
 Corresponding
resistor is not dial
 The files of main stop
GSD does not set
sound
131
Fault tracking
What to do
 Check the environment
and avoid the
interference source
 Change the hardware
and ask for service
 Check the keypad
wires and ensure
whether there is
mistake
 Change the hardware
and ask for service
 Repack-up the data in
the keypad
 Check related setting
 Check the environment
and avoid the
interference influence

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive 200L and is the answer not in the manual?

Questions and answers

Table of Contents