Put modules away in antistatic bags for future use.
NOTE:
The gateway has an ESD socket at both the front and rear.

Laser safety

WARNING!
• Disconnected optical fibers or transceiver modules might emit invisible laser light. Do not stare
into beams or view directly with optical instruments when the gateway is operating.
• Before you remove the optical fiber connector from a fiber port, execute the
command in interface view to shut down the port.
CAUTION:
• Insert optical fiber caps into open optical fiber connectors to protect them from contamination and
ESD damage.
• Insert dust plugs into open fiber ports and transceiver module ports to protect them from
contamination and ESD damage.

Examining the installation site

The gateway must be used indoors. To ensure the correct operation and long service life of your
gateway, the installation site must meet the requirements in this section.

Weight support

Make sure the floor can support the total weight of the rack, chassis, and accessories. Additionally,
the floor loading plan must also consider system expansion, such as adding more modules. For
more information, see "Appendix B Technical Specifications."

Space

For easy installation and maintenance, make sure the following requirements are met:
Make sure the rack has enough space (in height and depth) to accommodate the gateway.
The rack allows front and rear access to the gateway.
A minimum clearance of 1.2 m (3.94 ft) is reserved between the rack and walls or other devices.
For more information about the chassis dimensions, see "Appendix B Technical Specifications."
Table 1 Gateway dimensions and rack requirements
Model
M9000-AI-E8
Chassis dimensions
Height—264 mm (10.39 in)
Width—440 mm (17.32 in)
Depth—977 mm (38.46 in)
857 mm (33.74 in) for the
chassis
90 mm (3.54 in) for the cable
management brackets at the
Rack requirements
A minimum of 1.1 m (3.61 ft) in depth
(recommended).
A minimum of 140 mm (5.51 in) between
the front rack posts and the front door.
A minimum of 950 mm (37.40 in) between
the front rack posts and the rear door.