H3C SecPath M9000-AI-E8 Installation Manual page 19

Multi service security gateway series
Hide thumbs Also See for SecPath M9000-AI-E8:
Table of Contents

Advertisement

Item
Ventilation
Power supply
Grounding
Temperature
Humidity
Cleanliness
EMI prevention
Safety precautions
Accessories
Reference
Requirements
the equipment room.
There is a minimum clearance of 1200 mm
(47.24 in) between the rack and walls or other
devices.
There is a minimum clearance of 300 mm
(11.81 in) around the inlet and outlet air vents.
A good ventilation system is available at the
installation site.
The power supply system can output enough
power to maintain the device operation.
An uninterrupted power supply (UPS) is
available.
The power-off switch in the equipment room is
located so that the power can be immediately
shut off when an accident occurs.
The grounding specifications for the
equipment room comply with national and
industry standards.
All communication devices in the equipment
room are reliably grounded.
The working earthing and protective earthing
systems of the communication power supplies
use the same earthing conductor set with the
protective earthing system of the
communication devices.
0°C to 45°C (32°F to 113°F).
5% RH to 95% RH (noncondensing).
Dust concentration ≤ 3 × 104 particles/m
No visible dust on desk within three days.
Take effective measures to protect the power
system from the power grid system.
Separate the operation ground of the gateway
from the grounding device or lightning
protection grounding device as far as
possible.
Keep the gateway far away from radio
stations, radar and high-frequency devices
working in high current.
Use electromagnetic shielding when
necessary.
The gateway is far away from any heat source
and moist area.
The emergency power switch in the
equipment room is located.
Installation accessories provided with the gateway.
Documents shipped with the gateway.
Online documents.
8